Article 9
  1. As part of its planning of remote server room, an organization shall comply with the building and fire protection regulations promulgated by the government, with supporting facilities being taken into consideration, including power supply, HVAC arrangement, environment monitoring and warning system.
  2. Category 1 organizations shall have remote backup server room.
  3. Category 1 organizations shall install the main server room with the infrastructure enabling backup mechanism, such as double feeder lines, uninterruptible power system (UPS) designed for server room, power generator designed for server room, two or more telecommunication operators, and two or more external network lines.
  4. Category 1 organizations shall ensure its main server room and remote backup server room have sufficient power, water and gas supplies, sufficient for 72 hours of operation in the event of a supply interruption.
  5. When evaluating relocation of an existing server room or establishment of a new server room, an organization shall consider the following:
    1. With reference to the Server Room Remote Backup Mechanism Reference Guide by the Executive Yuan, the organization shall ensure the locations of its main server room and remote backup server room are unlikely to be affected by the same interruption risk incident (for example, in the same earthquake belt, in the same power supply area), or the distance of the main server room and remote backup server room is more than 30 kilometers.
    2. An organization shall consider the geological condition, natural disaster, man-made disaster (whether in the proximity of a nuclear power plant, a factory where chemical products or explosives are processed, directly under the aviation route near an airport, hospital with high traffic of patients, area with a high public security risk), facilities (water, power, gas supplies and online connection), transportation convenience, and staff’s commute time, etc. when determining the location.
    3. An organization is advised to consider if too many enterprises in the same industry are sharing the same server room.